| MPD-CD1-BS.50AB-SC25SZ-FZ-5.N16-5.N10-M1 -Temporary Power Distribution System |
Ratings |
| Line-in Cord: 25' #6/3 AWG TYPE SOOW Cord |
Max Primary OCP: 50A @ 600V |
| Line-in Cord Cap: Not Included - Requires Minimum Use Device 50A @ [600V] (**Customer Provided**) |
Max Secondary Output: 104.2A @ 240V |
| Primary Voltage (V): 600V AC |
NEMA 3R Indoor or Outdoor Use |
| Primary Phase (PH): 1-Phase (1PH) |
NEMA 3R In-Use Weather Shield |
| Primary Frequency (HZ): 60 Hz (60-cycles) |
Made in the USA |
| Primary Breaker: (1) 50A 2P MCCB [600V] |
NRTL Certified to UL 1640 |
| Primary Protection: MCCB Circuit Breaker |
NRTL Certified to CSA C22.2 No. 14 |
| Transformer (KVA): 25KVA 600V to 120/240V 1PH N3R |
 |
| Secondary Voltage (V): 120/240V AC |
Powder Coat Finish Standards: |
| Secondary Phase (PH): 1-Phase (1PH) |
Complies with ASTM D-523 |
| Secondary Frequency (HZ): 60 Hz (60-cycles) |
Complies with ASTM D-3359 |
| Secondary Panel: 120/240 1PH 104.2A MLO N3R |
Complies with ASTM D-522 |
| Secondary Breakers: (5) 20A 2P GFCI-MCB [250V]; (5) 20A 1P MCB [125V] |
Complies with ASTM D-3363 |
| Secondary Outlets: (5) 6-20R NEMA SPLX [250V]; (5) 5-20R NEMA DPLX GFCI [125V] |
Complies with ASTM D-2794 |
| Secondary Protection: MCB Circuit Breakers; GFCIs; Weather-proof Covers |
 |
| Form Factor: Blue Powder Coated MGL Dolly Cart w/ Run Flat Tires
|
 |
| Front Cover: Weatherproof Lid w/ Front-located Handle and Lock |
 |
| Cover Locking Position: Upward w/ Internal Locks on Both Sides of the Lid |
 |
| Vibration Isolators: Transformer and Breakers |
 |
| Drain Plug: Panel |
 |
| Cart Material: Steel |
 |
| Cart Finish: High-strength TGIC Polyester Powder Coated Blue |
| Cart Handle Orientation: Horizontal |
| Lifting Eyelet: (1) Center Point |
Toll Free:Â 1-800-369-6671 |
| No-flat Tires: (2) Black |
Intl:Â 1-214-616-6180
|
| Dimensions: 41"-W x 30"-D x 66.5"-H |
| Weight: 350 lbs |
| Larson Electronics manufactures a wide variety of custom power distribution systems. The pictures displayed for this unit are a general representation of form factor and may not accurately represent this exact configuration in every detail due to being custom builds. The specifics for this configuration are listed in the specification table and one-line diagram. |
*All grounding shall comply with state and local codes and meet the minimum requirements of the National Electronic Code section 250* |